Electrical Contct
rating
:
|
1NO+1NC
2NO+2NC
|
|
|
Continuous Current
(1th2)
|
10A
|
|
|
Rated Voltage A.
C.
:
|
500V
|
|
|
D. C.
:
|
600V
|
|
| Permissible
ambient temperature
: |
-40ºC
to +85ºC |
|
|
|
|
Mechanical Life
:
|
15 million Switching
cycles.
|
|
| Contact
Life A.C. |
| Breaking
Current -A |
1
|
3
|
6
|
10
|
| Switching
Cycles-million |
15
(11)
|
5
(4)
|
2.5
(1.8)
|
1
(0.7)
|
|
|
Frequency of operation
:
|
6000 cycles/hour
|
|
|
|
|
|
|
Making and breaking
capacity
:
and operational current -
40 - 60 Hz, P.f. 0.3 to 1
|
AC 11 duty
|
|
|
|
|
Voltage
V
|
Rated
Operating current
(le)
A
|
Rated
making
capacity
A
|
Rated
breaking
capacity
A
|
|
24
|
6(3)
|
90(30)
|
60(30)
|
|
125
|
6(3)
|
90(30)
|
60(30)
|
|
220
|
6(3)
|
90(30)
|
60(30)
|
|
380
|
6(3)
|
90(30)
|
60(30)
|
|
415
|
4(3)
|
90(30)
|
60(30)
|
|
500
|
4(3)
|
90(30)
|
60(30)
|
|
|
|
|
|
|
|
| |
|
|
|
Breaking Capacity
- D.C.
|
|
Voltage
|
Resistive
load(DC1)
|
Inductive
load
(DC11)
|
|
V
|
A
|
A
|
|
24
|
10(7)
|
10(7)
|
|
110
|
2.2(1.5)
|
1.3(0.91)
|
|
220
|
0.9(0.62)
|
0.4(0.28)
|
|
440
|
0.4(0.28)
|
0.2(0.14)
|
|
600
|
0.3(0.21)
|
0.14(0.1)
|
|
|
| |
|
|
|
|
|
Electrical Contact
rating
|
|
|
|
2NO+2NC
|
|
AC
11 rating
|
Double
pole:
|
|
|
2
No + 2NC
|
|
|
Changeover
contacts
|
|
110V
|
3.0A
|
|
240V
|
1.5
A
|
|
440V
|
0.5A
|
|
600V
|
0.6A
|
|
DC
11 rating
115V
230V
400V
|
|
Single
Throw
|
Double
throw
|
|
1.0A
|
0.2A
|
|
0.3A
|
0.1A
|
|
0.1A
|
|
|
|